Performance of an integrated solar absorption cooling system in a sub-tropical region

Darkwa, Jo and Fraser, S. (2012) Performance of an integrated solar absorption cooling system in a sub-tropical region. International Journal of Low-Carbon Technologies, 7 (3). pp. 199-207. ISSN 1748-1317

Full text not available from this repository.

Abstract

Evaluation of an integrated solar absorption cooling system located in a sub-tropical region has been carried out. Analysis of the results revealed an operational efficiency of 61% for the solar collectors at a mean differential temperature forumla of 51°C when compared with the manufacturer's rating of 70% at 60°C. The absorption chiller did, however, perform quite satisfactorily and achieved a coefficient of performance of 0.69 when compared with the manufacturer's rating of 0.7. There is however the need for the hot water supply system to be optimized as well as provision for supplementary heat source in order to maintain the appropriate operating temperature during low solar radiation levels.

Item Type: Article
RIS ID: https://nottingham-repository.worktribe.com/output/709999
Keywords: solar air-conditioning system; absorption chiller; collector efficiency; COP
Schools/Departments: University of Nottingham, UK > Faculty of Engineering
Identification Number: https://doi.org/10.1093/ijlct/cts024
Depositing User: LIN, Zhiren
Date Deposited: 20 Oct 2017 07:43
Last Modified: 04 May 2020 16:32
URI: https://eprints.nottingham.ac.uk/id/eprint/47318

Actions (Archive Staff Only)

Edit View Edit View