DC fault ride-through capability and STATCOM operation of a HVDC hybrid voltage source converter

Feldman, Ralph, Farr, Ewan, Watson, Alan James, Clare, Jon C. and Wheeler, Patrick (2014) DC fault ride-through capability and STATCOM operation of a HVDC hybrid voltage source converter. IET Generation, Transmission & Distribution, 8 (1). pp. 114-120. ISSN 1751-8695

Full text not available from this repository.

Abstract

HVDC transmission systems are becoming increasingly popular when compared to conventional AC transmission methods. HVDC voltage source converters (VSC) can offer advantages over traditional HVDC current source converter topologies; as such, it is expected that HVDC-VSCs will be further exploited with the growth of HVDC transmission. This paper presents the DC fault ride through capability and new STATCOM modes of operation for the recently published Alternate Arm Converter (AAC), intended for the HVDC market. Operation and fault ride through of the converter during a local terminal to terminal short circuit of the DC-Link is demonstrated; during the fault STATCOM operation is also demonstrated.

Item Type: Article
RIS ID: https://nottingham-repository.worktribe.com/output/720895
Additional Information: This paper is a postprint of a paper submitted to and accepted for publication in IET Generation, Transmission & Distribution and is subject to Institution of Engineering and Technology Copyright. The copy of record is available at IET Digital Library
Keywords: HVDC power convertors, HVDC power transmission, Static VAr compensators
Schools/Departments: University of Nottingham, UK > Faculty of Engineering > Department of Electrical and Electronic Engineering
Identification Number: 10.1049/iet-gtd.2012.0713
Depositing User: Burns, Rebecca
Date Deposited: 18 Jul 2016 08:02
Last Modified: 04 May 2020 16:41
URI: https://eprints.nottingham.ac.uk/id/eprint/35007

Actions (Archive Staff Only)

Edit View Edit View